Specifications

Product Family

Eaton Tripp Lite PDU3 three-phase switched PDU, 0U vertical

Featured Models

PDU3VSR6G30 (10 kW), PDU3XVSR6G60A (25.2 kW, TAA variant PDU3XVSR6G60ATAA)

PDU3VSR6G30 Output

10.0 kW at 240 V, 9.6 kW at 230 V, 8.6 kW at 208 V

PDU3VSR6G30 Input

IEC-309 30 A Blue (3P+E), 200/208/220/230/240 V, 24 A maximum, 6 ft cord

PDU3VSR6G30 Outlets

30 switched 208 V outlets — (24) C13 + (6) C19, 8 C13 and 2 C19 per phase

PDU3VSR6G30 Breakers

3 x 20 A double-pole branch-rated circuit breakers, one per output phase

PDU3XVSR6G60A Output

25.2 kW at 415/240 V, 24.3 kW at 400/230 V, 23 kW at 380/220 V

PDU3XVSR6G60A Input

IEC-309 60 A Red (3P+N+E), 415 V three-phase, 35 A maximum (agency derated)

PDU3XVSR6G60A Outlets

(12) C13 + (12) C19 in six separately breakered 20 A single-phase load banks

Metering Accuracy

+/-1% billing-grade monitoring per outlet, per breaker bank and per phase

Outlet Control

Individually switched outlets: on, off, recycle or electronic lock-off

Load Sequencing

Custom-programmed power-up and power-down sequences prevent inrush overloads

Local Interface

Digital LCD with 180 degree rotation, six status LEDs and one LED per outlet

Outlet Status LEDs

Green below 80% bank load, yellow above 80%, red off or undervoltage, flashing red on breaker trip

Environmental Sensing

Optional ENVIROSENSE temperature and humidity sensor per rack

Rack Access

Up to 4 optional SRSWITCH door sensors for access notification

Network

10/100 Mbps auto-sensing, DHCP or manual configuration, real-time clock backup

Protocols

HTTP/HTTPS, SMTP, SNMPv1/v2/v3, Telnet, SSH, FTP, DHCP, BOOTP, NTP

Management

PowerAlert Network Management System, tiered administrator and guest access

Form Factor

0U vertical, 70 in / 1778 mm, toolless button-mount

Cable Retention

Plug-lock inserts secure C14 and C20 cords against vibration

Compliance

UL listed; TAA-compliant variants available; 2-year limited warranty

Overview

Eaton's Tripp Lite PDU3 family is built for the three-phase, high-density cabinets that AI and GPU clusters now occupy. Two models bracket the range: the PDU3VSR6G30 offers 10 kW at 240 V through 30 switched outlets, while the PDU3XVSR6G60A reaches 25.2 kW at 415/240 V through 24 outlets split across six separately breakered load banks.

Both units switch and meter every individual receptacle, reporting at +/-1% billing-grade accuracy per outlet, per breaker bank and per phase. That granularity is what makes them useful in multi-tenant AI halls: a colocation operator can bill a customer for exactly the energy their GPU nodes consumed, and remotely recycle a single hung node without touching the rack.

Key Benefits

Per-receptacle switching and billing-grade metering enable accurate tenant chargeback and remote fault recovery. Up to 25.2 kW in a single zero-U strip matches the power density of modern GPU chassis. PowerAlert NMS with SNMPv3 and SSH integrates with existing DCIM workflows, and ENVIROSENSE plus door sensors add rack-level environmental and access telemetry.

Applications

High-density AI and HPC racks, multi-tenant colocation with per-outlet billing, lab racks with remotely rebootable test nodes, and any three-phase deployment needing 10 to 25 kW of switched distribution in zero rack units.

Request a Quote — EATON TRIPP LITE PDU3 SWITCHED — 3-PHASE RACK PDUS TO 25.2 KW

QS Compute — global B2B supply of AI computing hardware, edge AI systems and accelerators. Volume pricing, 15-day sample lead time.

Get Your Quote →

Related Products

APC NetShelter Rack PDU 2G — Metered & Switched PDUs CyberPower Rack PDU — Switched & Metered-by-Outlet Raritan PX4 — Intelligent Rack PDU Vertiv Geist uPDU — Universal Rack PDU