Specifications
Product Family
Eaton Tripp Lite PDU3 three-phase switched PDU, 0U vertical
Featured Models
PDU3VSR6G30 (10 kW), PDU3XVSR6G60A (25.2 kW, TAA variant PDU3XVSR6G60ATAA)
PDU3VSR6G30 Output
10.0 kW at 240 V, 9.6 kW at 230 V, 8.6 kW at 208 V
PDU3VSR6G30 Input
IEC-309 30 A Blue (3P+E), 200/208/220/230/240 V, 24 A maximum, 6 ft cord
PDU3VSR6G30 Outlets
30 switched 208 V outlets — (24) C13 + (6) C19, 8 C13 and 2 C19 per phase
PDU3VSR6G30 Breakers
3 x 20 A double-pole branch-rated circuit breakers, one per output phase
PDU3XVSR6G60A Output
25.2 kW at 415/240 V, 24.3 kW at 400/230 V, 23 kW at 380/220 V
PDU3XVSR6G60A Input
IEC-309 60 A Red (3P+N+E), 415 V three-phase, 35 A maximum (agency derated)
PDU3XVSR6G60A Outlets
(12) C13 + (12) C19 in six separately breakered 20 A single-phase load banks
Metering Accuracy
+/-1% billing-grade monitoring per outlet, per breaker bank and per phase
Outlet Control
Individually switched outlets: on, off, recycle or electronic lock-off
Load Sequencing
Custom-programmed power-up and power-down sequences prevent inrush overloads
Local Interface
Digital LCD with 180 degree rotation, six status LEDs and one LED per outlet
Outlet Status LEDs
Green below 80% bank load, yellow above 80%, red off or undervoltage, flashing red on breaker trip
Environmental Sensing
Optional ENVIROSENSE temperature and humidity sensor per rack
Rack Access
Up to 4 optional SRSWITCH door sensors for access notification
Network
10/100 Mbps auto-sensing, DHCP or manual configuration, real-time clock backup
Protocols
HTTP/HTTPS, SMTP, SNMPv1/v2/v3, Telnet, SSH, FTP, DHCP, BOOTP, NTP
Management
PowerAlert Network Management System, tiered administrator and guest access
Form Factor
0U vertical, 70 in / 1778 mm, toolless button-mount
Cable Retention
Plug-lock inserts secure C14 and C20 cords against vibration
Compliance
UL listed; TAA-compliant variants available; 2-year limited warranty
Overview
Eaton's Tripp Lite PDU3 family is built for the three-phase, high-density cabinets that AI and GPU clusters now occupy. Two models bracket the range: the PDU3VSR6G30 offers 10 kW at 240 V through 30 switched outlets, while the PDU3XVSR6G60A reaches 25.2 kW at 415/240 V through 24 outlets split across six separately breakered load banks.
Both units switch and meter every individual receptacle, reporting at +/-1% billing-grade accuracy per outlet, per breaker bank and per phase. That granularity is what makes them useful in multi-tenant AI halls: a colocation operator can bill a customer for exactly the energy their GPU nodes consumed, and remotely recycle a single hung node without touching the rack.
Key Benefits
Per-receptacle switching and billing-grade metering enable accurate tenant chargeback and remote fault recovery. Up to 25.2 kW in a single zero-U strip matches the power density of modern GPU chassis. PowerAlert NMS with SNMPv3 and SSH integrates with existing DCIM workflows, and ENVIROSENSE plus door sensors add rack-level environmental and access telemetry.
Applications
High-density AI and HPC racks, multi-tenant colocation with per-outlet billing, lab racks with remotely rebootable test nodes, and any three-phase deployment needing 10 to 25 kW of switched distribution in zero rack units.
Request a Quote — EATON TRIPP LITE PDU3 SWITCHED — 3-PHASE RACK PDUS TO 25.2 KW
QS Compute — global B2B supply of AI computing hardware, edge AI systems and accelerators. Volume pricing, 15-day sample lead time.