Specifications

Product Family

APC NetShelter Rack PDU 2G — metered, metered-by-outlet and switched zero-U PDUs

Featured Models

AP8853 (metered), AP8886 (three-phase metered), AP8941 / APDU9941 (switched)

AP8853 Input

IEC 309 32 A 2P+E, 200 / 208 / 230 V, 50/60 Hz, 3 m cord

AP8853 Output

(36) IEC 320 C13 + (6) IEC 320 C19 — 7,400 VA at 32 A

AP8886 Output

Zero-U three-phase: 22 kW at 230 V 32 A, or 17.3 kW at 230 V 24 A

AP8886 Outlets

(30) C13 + (12) C19 — 42 outlets total, three-phase balanced

AP8941 (Switched)

30 A, 200 / 208 V, (21) C13 + (3) C19 — superseded by APDU9941

Metering

Volts, amps, real power (kW) and energy (kWh) actively measured, displayed and logged

Alarms

User-defined thresholds warn of overload before circuits trip

Local Display

Onboard LCD showing current, voltage, power and energy per PDU

Remote Management

EcoStruxure IT, Web interface, SNMP and Command Line Interface

Daisy Chain

Monitor up to 4 PDUs from a single IP address; local USB firmware port

Operating Temperature

-5 to 45 C (23 to 113 F); zero-U designs rated to 60 C capability

Form Factor

Zero-U vertical, 1791 x 56 x 44 mm (70.5 x 2.2 x 1.72 in)

Weight

6.93 kg (15.24 lb) net for AP8853

Mounting

Toolless vertical button-mount inside NetShelter racks

Environmental Sensors

Optional temperature and humidity probes per rack

Colour

Black

Regulatory

UL and RoHS compliant; verified product environment profile (carbon, scope 3, end of life)

Overview

The APC NetShelter Rack PDU 2G family is the reference rack-level power distribution line for AI, HPC and dense enterprise racks. Every unit in the family actively measures, displays and logs volts, amps, real power and energy, so operators know exactly how much of a 42-outlet strip is consumed before adding another GPU node.

Three deployment profiles cover most AI racks: the AP8853 delivers 7.4 kVA single-phase through 36 C13 and 6 C19 outlets; the AP8886 steps up to three-phase 22 kW with 42 outlets for high-density GPU cabinets; and the switched AP8941 / APDU9941 adds per-outlet remote on/off and recycle for locked-up compute nodes. All models integrate with EcoStruxure IT and support daisy-chaining up to four PDUs from one IP address.

Key Benefits

Per-outlet and per-PDU energy data enables customer-level power billing and capacity planning in shared AI racks. Switched models let operators recycle unresponsive GPU servers remotely instead of dispatching a technician. Zero-U vertical mounting preserves all rack units for compute, and the wide -5 to 45 C rating suits hot-aisle deployment behind dense GPU trays.

Applications

AI and GPU cluster racks, HPC cabinets, colocation cages with sub-metering, edge data centres with limited rack U, and any deployment requiring SNMP-visible rack power telemetry for capacity and billing.