Specifications

Product Family

nVent RDHX PRO rear door cooling unit (Schroff-branded data solutions)

Cooling Capacity

Up to 78 kW per rack; 68 kW at 14 degrees C supply water, 44 kW at 24 degrees C

Variants

Passive (240 mm deep) and Active (281 mm deep) rear door cooler

Rack Sizes

Standard sizes for 42U, 47U, 48U and 52U data centre racks

Rack Widths

600 mm and 800 mm

Dry Weight

200 kg

Depth

240 mm passive / 281 mm active; adapter frame adds approximately 127 mm

Adapter Frame

Approximately 127 mm deep solid frame housing the RDHX and the complete plumbing / wetted path — no wetted material penetrates into the rack, which increases leak safety

Top Cover

Cover panel with cutouts for flexible hoses and cabling

Warm Water Operation

Runs comfortably on 57 degrees F (14 degrees C) warm water, enabling free cooling and a substantially lower facility energy cost

Cooling Performance

Published performance curves in W/K against cold air flow from 1,500 to 9,000 m3/h at 20-80 l/min water flow

Supply Temperture Headroom

Performance is quoted at both 14 degrees C and 24 degrees C supply so operators can plan for higher water temperatures

Leak Management

Condensate drain options (top feed, 600 W and 750 W) and an optional leak detection package

Installation

Mounts to the rack rear door; can be installed in live environments and added incrementally for retrofit

Floor Space

No additional floor space or ceiling headroom required — frees white space otherwise consumed by CRAH units

Alignment

Matches ASHRAE Table 3.1 2021 thermal guidelines for data centre supply temperatures

Overview

The RDHX PRO is nVent's answer to racks that have outgrown air cooling but are not yet ready for full direct-to-chip liquid. It is a rear door cooling unit rated to 78 kW, mounted directly on the back of the rack so the coil sits immediately downstream of the server exhaust.

The design goal is warm water operation. At 14 degrees C supply water the unit removes 68 kW; at 24 degrees C it still removes 44 kW. Being able to run on 24 degrees C instead of chilled water in the 7-12 degrees C range is what lets a facility use free cooling for a much larger share of the year, and it is the single biggest lever on the unit's operating cost.

Mechanically, the RDHX and its entire wetted path live in an approximately 127 mm adapter frame outside the rack, so no wetted material penetrates into the IT compartment. Combined with the condensate drain and optional leak detection package, that keeps water outside the equipment enclosure. The unit is offered in a 240 mm passive form and a 281 mm active form with fans.

Key Benefits

Up to 78 kW per rack at rack level. 68 kW on 14 degrees C warm water, 44 kW on 24 degrees C for free-cooling economics. Wetted path stays outside the rack in a 127 mm adapter frame. No floor or ceiling footprint added. Retrofit-friendly — can be added incrementally in live environments.

Applications

High-density AI and HPC racks; retrofit of air-cooled halls toward liquid cooling; free-cooling-optimised facilities; OCP-style racks; colocation density upgrades where floor space is fixed.