Specifications

Product

nVent Open CDU 5.0 (Project Deschutes)

Specification

Built to Google Project Deschutes 5.0 (OCP)

Type

High-pressure liquid-to-liquid coolant distribution unit

Cooling capacity

Up to 2 MW

Flow rate

Up to 500 gpm (secondary)

Pumps

N+1 sealless pumps

Drives

Low-harmonic variable-frequency drives (VFD)

Approach temperature

3 °C

Secondary pressure available

~80–90 psi

Primary loop dP

15–27 psi

Isolation

Full isolation between facility water and technology cooling circuits

Power consumption

74 kW

Weight

6,910 lb wet / 5,310 lb dry

Dimensions (W×H×D)

65.25 × 91.44 × 40.29 in

Compatibility

NVIDIA GB200/GB300-class racks and Google TPU 'Ironwood'

MPN

Deschutes Open CDU 5.0

Overview

nVent's Project Deschutes Open CDU 5.0 is a high-pressure, liquid-to-liquid coolant distribution unit built directly to Google's Project Deschutes 5.0 specification and contributed to the Open Compute Project. It delivers up to 2 MW of cooling at a 3 °C approach temperature and 500 gpm of secondary flow.

The unit uses N+1 sealless pumps and low-harmonic VFD drives, with full isolation between the facility-water and technology-cooling circuits. It is positioned as the cooling foundation for GB200/GB300-class and next-generation TPU deployments, and shares nVent's common control platform with the CX121 row CDU and CZ61/CZ62 rack CDUs.

Key Benefits

2 MW per unit at a 3 °C approach temperature. OCP/Google Deschutes 5.0 open-standard design. N+1 sealless pumps with full facility/technology loop isolation.

Applications

Hyperscale AI data centers, OCP-based rack deployments, NVIDIA GB200/GB300-class racks and Google TPU training pods requiring 2 MW-scale liquid-to-liquid cooling.

Request a Quote — NVENT PROJECT DESCHUTES OPEN CDU 5.0 — 2 MW OCP CDU

QS Compute — global B2B supply of AI computing hardware, edge AI systems and accelerators. Volume pricing, 15-day sample lead time.

Get Your Quote →

Related Products

nVent CX121 Row-Based CDU nVent CZ61/CZ62 Rack CDUs LiquidStack CDU 1 MW