Specifications

Product

LiquidStack CDU-1MW universal coolant distribution unit (CDU)

Cooling Capacity

Up to 1,350 kW (1 MW class) of direct-to-chip cooling at a 13°C TCS delta-T and 4°C approach

Capacity by Delta-T

1,004 kW at 10°C delta-T; 1,202 kW at 12°C delta-T; 1,350 kW at 13°C delta-T

Maximum Flow Rate

1,500 litres per minute on the technology cooling system (TCS) loop

Glycol Rating

PG 25 propylene glycol

Heat Dissipation Ratio

1.15 lpm/kW at 13°C delta-T (1.25 lpm/kW at 12°C, 1.50 lpm/kW at 10°C)

Design Philosophy

Elevated operating water temperatures, narrow approach temperatures and higher differential pressure operation

Pumps

Dual hot-swappable variable-speed-drive (VSD) pumps

Heat Exchanger

316 stainless steel plate heat exchanger

Electrical

Integrated automatic transfer switch (ATS) with controller supercapacitor

Control Valve

2-way electronic pressure-independent control valve (E-PICV) or 3-way control valve

Filtration

Dual 25-micron filtration on the coolant loop

Dimensions

Row-style form factor: 900 mm wide x 1,242 mm deep x 2,200 mm high (35 in x 49 in x 87 in)

Weight

911 kg dry / 1,165 kg operating / 1,100 kg shipping (2,004 / 2,563 / 2,420 lb)

Facility Water Temperature

10°C to 45°C (50°F to 113°F) facility water supply range

Power Input

380-480 VAC, 50/60 Hz, 3-phase with neutral and earth; MOP 70 A, MCA 62.5 A, FLA 47 A

Power Consumption

23 kW total, approximately 11 kW per pump

Coolant Volume

78.92 L (20.85 gal) TCS loop and 119.24 L (31.50 gal) facility loop

Noise

Under 68 dBA at 3 m at full load

Protocols

MODBUS TCP/IP, RESTful API, BACnet IP and SNMP

Control Interface

7″ colour display with live P&ID view; temperature, pressure and flow sensors across TCS and facility loops

Features

Environmental monitoring with dew point control, PN16 static pressure rating, unit grouping of setpoints, rotation schedules and duty cycles

Efficiency Outcomes

36% reduction in energy used for cooling, 48% CAPEX reduction versus air cooling, 62% reduction in data center white space, 25% TCO improvement over 20 years

Certification

ETL listed with CE and CSA certification; top or bottom piping and electrical entry with optional floorstand

Options

N+1 component upgrade (expansion tanks, sensors), remote firmware upgrade, rope-type leak sensor and pump dry-run protection

Overview

The LiquidStack CDU-1MW is a row-form-factor coolant distribution unit aimed squarely at the thermal envelope of current AI chips and servers. A single unit delivers up to 1,350 kW of direct-to-chip cooling — 1,004 kW at a 10°C loop delta-T, 1,202 kW at 12°C and the full 1,350 kW at 13°C with a 4°C approach temperature — while moving up to 1,500 litres per minute of PG25 glycol.

The design is built around elevated operating water temperatures and narrow approach temperatures, which is what makes it suitable for both new AI data halls and retrofit facilities: warm facility water lets the heat rejection path avoid chillers, and the unit is right-sized for a data hall rather than a single rack. Hardware resilience includes dual hot-swappable VSD pumps, a 316 stainless steel plate heat exchanger, an integrated automatic transfer switch with controller supercapacitor, a 2-way electronic pressure-independent control valve and dual 25-micron filtration.

LiquidStack reports a 36% reduction in cooling energy, a 48% CAPEX reduction against air cooling, a 62% reduction in white space and a 25% improvement in 20-year TCO. Management is handled through MODBUS TCP/IP, RESTful API, BACnet IP and SNMP with a 7-inch colour display showing a live P&ID view, plus dew point control and full temperature, pressure and flow instrumentation across both loops.

Key Benefits

Megawatt-class distribution in one unit: up to 1,350 kW replaces several smaller CDUs, reducing piping, footprint and control complexity per data hall. Retrofit-friendly thermodynamics: high entering water temperatures and narrow approach temperatures let existing facilities host direct-to-chip loads without new chiller plant. Serviceable without downtime: dual hot-swappable VSD pumps, a controller supercapacitor holding the ATS through transfers, and rack-free row placement keep maintenance out of the critical path.

Applications

Direct-to-chip liquid cooling for Gen AI, large language model and HPC clusters, new-build AI data halls, retrofit of air-cooled halls with high-density racks, colocation white space reclamation, and CDU capacity expansion where supply is constrained.

Request a Quote — LIQUIDSTACK CDU-1MW COOLANT DISTRIBUTION UNIT — 1,350 KW DIRECT-TO-CHIP, 36% LESS COOLING ENERGY

QS Compute — global B2B supply of AI computing hardware, edge AI systems and accelerators. Volume pricing, 15-day sample lead time.

Get Your Quote →

Related Products

200 kW Coolant Distribution Unit CoolIT CHx2000 CDU nVent RackChiller RDC Dell PowerCool CDU C7000