Specifications

Products

LCP Rack CW / CWG · LCP Inline CW / CWG · LCP Inline EC

Model Numbers

LCP Rack CW 3313130 · LCP Inline EC SK 3300.470

Max Cooling Output

30 kW

Useful Cooling Output

27-30 kW at L42W15

Cooling Medium

Water (air/water heat exchanger)

Water Connections

DN 40 (G 1½″ external thread)

Permissible Operating Pressure

10 bar

Air Throughput (fans)

Up to 5,000 m³/h

Rated Voltage

200-240 V AC 1~ 60 Hz; 346-415 V AC 3~ 50/60 Hz

Rated Current

2.2-6.5 A depending on configuration

Max Connected Load

1,490 W (3 fan modules) / 2,990 W (6 fan modules)

Duty Cycle

100 %

Fans

EC fans, infinitely variable, hot-swappable with the system running

Temperature Control

Linear fan control with two-way control valve

Control Input

Server air intake temperature

Noise Level

Max 88 dB(A) at 1 m (3-fan configuration)

Enclosure Finish

RAL 7035

Cooling Capacity Range

CW up to 30 kW; DX variants 5-20 kW via inverter scroll compressor

Optional Extras

Fan module 3313.016, touchscreen 3311.030, hose 3311.040, condensate pump 3312.012

Manufacturer

Rittal

Overview

Rittal's Liquid Cooling Package is a family of air/water heat exchangers that bolt onto an IT rack and remove heat at the rack boundary, rather than a CDU that feeds cold plates. The CW (chilled water) versions — LCP Rack CW/CWG (model 3313130) and LCP Inline CW/CWG, plus the LCP Inline EC at SK 3300.470 — are rated to 30 kW of useful cooling with water connections at DN 40 and a 10 bar working pressure.

The operating principle is simple: the unit draws hot exhaust air from the rear of the server enclosure, passes it through a water-cooled heat exchanger, and returns cooled air to the front of the rack or into the cold aisle. Because the heat leaves in water rather than air, the room-level CRAC load drops by the same amount, which is how a data hall can add high-density racks without re-engineering the perimeter air conditioning. It is the least invasive way to raise rack density in an existing air-cooled room.

Mechanically the units are built for serviceability: EC fans are infinitely variable and can be exchanged while the system runs, control is closed-loop on server intake temperature with a two-way valve, and the fan modules can be added in pairs (3 or 6 modules) to match the load. Noise is the main trade-off — up to 88 dB(A) at one metre on the three-fan configuration, which puts these units in machine-room rather than office-adjacent environments. Rittal also offers DX variants rated 5-20 kW using an inverter scroll compressor for sites with no chilled water available.

Key Benefits

30 kW of rack-level heat removal with no change to the servers. Heat leaves in water, cutting room CRAC load and raising achievable hall density. EC fans, hot-swappable with the system running reduce service downtime. Closed-loop control on server intake temperature with a two-way valve. DN 40 connections at 10 bar match standard hydronic infrastructure. Scalable fan modules (3 or 6) let capacity follow the load.

Applications

High-density racks in existing air-cooled data halls; IT cooling where perimeter CRAC capacity is exhausted; telecom and enterprise equipment rooms; laboratory and industrial IT enclosures; retrofit of rack cooling without facility water re-design; DX variant deployment where no chilled water is available.

Request a Quote — RITTAL LIQUID COOLING PACKAGE LCP INLINE CW / RACK CW — 30 KW RACK COOLING

QS Compute — global B2B supply of AI computing hardware, edge AI systems and accelerators. Volume pricing, 15-day sample lead time.

Get Your Quote →

Related Products

40 kW Rear-Door Heat Exchanger — RDHx nVent RackChiller RDC — Rear-Door Cooler 50 kW Coolant Distribution Unit