Specifications

Product Line

Vertiv Geist GU2 rack PDUs (rPDU)

PDU Families

Basic, Metered, Monitored, Switched and Switched with outlet-level metering

Outlet Relays

Bi-stable, magnetically latching relays hold their state without continuous power

Fail-Safe Behaviour

Relays open automatically when the rPDU is switched off or loses power

Outlet Sequencing

User-selected outlet sequencing activates on power restoration in the defined order

Energy Efficiency

Latching relays eliminate the standby energy consumed by continuously energised relay coils

Voltage Range

120 V to 415 V, single-phase and three-phase

Current Range

16 A to 60 A+ inputs depending on configuration

Power per PDU

Up to 17.2 kW per rack PDU in three-phase configuration

Outlet Types

C13 / C19 combinations and U-Lock locking receptacles, rated to 60 °C

Metering Levels

Unit level, circuit/breaker level and outlet level

Environmental Monitoring

Plug-and-play sensor ports for temperature, humidity, airflow, leak detection and door contacts

Remote Management

Network monitoring and outlet switching with SNMP and DCIM integration

Form Factor

Vertical (0U) and horizontal rack mounting

Overview

The GU2 generation is the switching layer of the Vertiv Geist rack PDU range. Its defining feature is the outlet relay: GU2 uses bi-stable, magnetically latching relays that hold their position without continuous power. Conventional switched PDUs keep a relay coil energised for every outlet that is switched on, which is measurable standby load in a rack 40 PDUs deep.

Latching relays also fix a recovery problem. When a GU2 rPDU is switched off or loses input power, the relays open automatically; when power returns, the previously configured outlet sequencing runs in the defined order. Servers, switches and storage therefore come up in the correct sequence instead of all drawing inrush simultaneously — which matters when 8-way GPU servers with multi-kilowatt supplies share a feed.

The GU2 range spans basic, metered, monitored and switched families with unit, breaker and outlet-level metering, 120–415 V inputs, and 60 °C rated C13/C19 and U-Lock outlets. It is the rPDU most often paired with high-density AI racks because both the metering granularity and the sequencing behaviour are aimed at exactly that load profile.

Key Benefits

Bi-stable latching outlet relays remove continuous coil power and guarantee defined outlet sequencing after an outage. Metering is available at unit, breaker and outlet level, and the 415 V three-phase models carry up to 17.2 kW in a single rack PDU.

Applications

AI and HPC racks with multiple multi-kilowatt GPU servers, cabinets requiring per-outlet power accounting, remote power cycling of unstaffed edge sites, colocation tenants who need billing-grade circuit metering, and any deployment where correct power-up sequencing protects the upstream breaker.

Request a Quote — VERTIV GEIST GU2 RPDU — SWITCHED & MONITORED RACK PDU WITH LATCHING RELAYS

QS Compute — global B2B supply of AI computing hardware, edge AI systems and accelerators. Volume pricing, 15-day sample lead time.

Get Your Quote →

Related Products

Vertiv Geist UPDU Vertiv PowerDirect 5000 800VDC Chicony CRPS / M-CRPS Power Supply Delta ORv3 18kW Power Shelf