Specifications
Product
ROL4000-48U65 in-row coolant distribution unit (CDU)
Type
Liquid-to-liquid (L2L), facility water to technology cooling system (TCS)
Cooling Capacity
2 MW (2,000 kW)
Approach Temperature
3 °C
Available Pressure
Up to 80 PSI for cold plate loops, control valves and manifolds
Form Factor
48U in-row
Architecture
Redundant pump design with standby bypass loop
Control
Dynamic condensation-free control; automatic coolant replenishing
Leak Management
Automatic leak detection with integrated monitoring
Application
Next-generation AI processors and high-density GPU racks
Facility Interface
Designed to reduce facility cooling load by raising supply temperatures
Typical Rack Density
Targets 100 kW+ per rack AI deployments
Vendor
Eaton Boyd Thermal (Boyd Corporation)
Service
Commissioning, in-region design collaboration and long-term maintenance
Also In Family
RAA32-10U2 10U L2A (32 kW) and RAA22-10U19 rack CDUs
Overview
The Eaton Boyd ROL4000-48U65 is an in-row, liquid-to-liquid coolant distribution unit rated at 2 MW of cooling capacity with a 3 °C approach temperature. It was developed specifically for next-generation technology cooling system (TCS) loops, delivering up to 80 PSI of available pressure to drive flow through high-performance cold plate loops, control valves and rack manifolds.
By operating at a narrow approach temperature the unit raises the return water temperature seen by the facility plant, which reduces or eliminates the need for facility chillers and lowers overall power usage effectiveness. Redundant pumps, a standby bypass loop, automatic coolant replenishing and automatic leak detection address the availability requirements of AI training clusters.
Boyd (now part of Eaton) supplies the full cooling ecosystem around the CDU: cold plates, rack manifolds, liquid loops, leak detectors, tubing and quick disconnects. The ROL4000 sits above the RAA32-10U2 10U liquid-to-air unit (32 kW) for sites without facility water.
Key Benefits
2 MW per unit for rack densities beyond 100 kW. 3 °C approach temperature reduces facility cooling load. 80 PSI available pressure for dense cold plate loops. Redundant pumps and bypass loop for continuous operation.
Applications
AI training and inference halls, hyperscale GPU clusters, colocation high-density halls, retrofits of air-cooled data centres to direct liquid cooling, and TCS loop deployments at 100 kW+ per rack.
Request a Quote — EATON BOYD ROL4000-48U65 — 2 MW IN-ROW LIQUID-TO-LIQUID CDU